About specific building environmental hygiene management standard

Last Updated April 1, 2022

This is the site of Health Sanitation Division, Health and Safety Department, Yokohama City Public Health Center. We provide information on the hygiene of buildings.
Please contact Health and Welfare Center Health Sanitation Division, the ward where the facility is located.

Building Environmental Sanitation Management Standards

When it falls under a specific building, its owners, occupants, etc. are obliged to maintain and maintain the specific building in accordance with certain standards specified by a Cabinet Order. In addition, owners of specific buildings are required to appoint a building environmental hygiene management engineer in order to supervise them so that maintenance is performed properly.
In addition, even if it is a building other than a specific building, there is an obligation to make efforts to maintain it according to the building environmental management standards used or used by many people. .

1 Air Environment

Air environment measurement
Air environment measurement 1/2 months (regular)

※Measurements are conducted at least twice a day at facilities with air conditioning equipment and mechanical ventilation equipment.
※Air conditioning equipment: Equipment that can purify the air and control the temperature, humidity and flow rate.
※Mechanical ventilation equipment: Equipment that can purify the air and adjust the flow rate and supply it.

Management standards for facilities that have air conditioning equipment (Article 2 of the Cabinet Order)
1 Amount of suspended dust 0.15 mg or less per 1 m3 of air
2 Containment of carbon monoxide 6 ppm or less
3 Carbon dioxide content 1,000 ppm or less
4 Temperature 18°C or more and 28°C or less
5 Relative humidity 40% or more and 70% or less
6 Air current 0.5m/second or less
7 Amount of formaldehyde 0.1 mg or less per 1 m3 of air

※For 1, calibration of the dust meter should be carried out regularly once a year or less.
※Temperature and relative humidity standards do not apply to mechanical ventilation equipment.
※For 7, complete new construction, extension, large-scale repair, and large-scale remodeling, and measure once from the start of use of the building to the latest from June 1 to September 30 .

2 Air conditioning equipment (cooling towers, humidifiers, etc.)

  • The water to be supplied must conform to the water quality standards stipulated in Article 4 of the Water Supply Law.
About drainage receiving, cooling tower and humidification equipment in air conditioning equipment
Inspection of dirt conditions Once every month during the start of use and during the period of use
Cleaning and water conversion Implement as necessary

※Even if the usage period is short, regular cleaning should be performed once a year or less.

  • Clean the cooling water pipes regularly once a year.

3 When supplying drinking water and domestic water (including central circulation hot water)

Hygiene measures related to water supply
Measurement of free residual chlorine 1/7 days (0.1ppm or more)
Cleaning of water storage tanks and hot water storage tanks 1/1 year (regular)

※In the case of combined residual chlorine, retain at least 0.4 ppm.
※If the supplied water may be significantly contaminated with pathogenic organisms, or if there is a possibility that it may contain a large amount of organisms or substances that may suspect that the pathogenic organisms are contaminated, free residual chlorine contained in the water at the hydrant shall be 0.2 ppm (1.5 ppm for combined residual chlorine).
※If the maintenance and management of the hot water supply equipment is performed appropriately (such as checking the temperature in the return pipe) and the water temperature of the water at the terminal hydrant is kept at 55 ° C or more, the water quality inspection of the content of free residual chlorine can be omitted.
※Reservoirs refer to water receiving tanks, elevated water tanks, etc.
※Regarding the cleaning of the hot water storage tank, the cleaning method differs depending on the conditions of the equipment, but as much as possible, use the same method as cleaning the water tank. In addition, it is desirable to carry out equipment that cannot use the same method as the water tank cleaning work due to a closed type, etc. as much as possible according to the situation. In addition, for equipment that cannot be cleaned, be sure to perform cleaning such as drainage.

  • Water quality inspection (when there is a water receiving tank that uses only water supplied from tap water or dedicated water supply as a water source, and central circulation type hot water supply)
Once within 6 months (* Items with * can be omitted up to once within 1 year)
Water quality inspection items Standard value Water quality inspection items Standard value
General bacteria 100 pieces/mL or less Chloride ion 200mg/L or less
Escherichia coli Not detected Evaporation residue* 500mg/L or less
Lead and its compounds* 0.01mg/L or less Organic matter (the amount of total organic carbon (TOC)) 3mg/L or less
Nitrate nitrogen and nitrite nitrogen 10mg/L or less pH value 5.8 or more 8.6 or less
Nitrite nitrogen 0.04mg/l or less Taste Not abnormal
Zinc and its compounds* 1.0mg/L or less Odor Not abnormal
Iron and its compounds* 0.3mg/L or less Chromaticity 5 degrees or less
Copper and its compounds* 1.0mg/L or less Turbidity 2 times or less

※As a result of the inspection, if the criteria are met, the number of items marked with * in the next inspection can be reduced.

Once between June 1 and September 30
Water quality inspection items Standard value Water quality inspection items Standard value
Chloric acid 0.6mg/L or less Bromic acid 0.01mg/L or less
Cyanide ions and cyanide chloride 0.01mg/L or less Total trihalomethane (chloroform, dibromo)
Chloromethane, bromodichloromethane and
The sum of the concentrations of each bromoform)
0.1mg/L or less
Chloroacetic acid 0.02mg/L or less Trichloroacetic acid 0.03mg/L or less
Chloroform 0.06mg/L or less Bromodichloromethane 0.03mg/L or less
Dichloroacetic acid 0.03mg/L or less Bromoform 0.09mg/L or less
Dibromochloromethane 0.1mg/L or less Formaldehyde 0.08mg/L or less

※About central circulation type hot water supply, we assume conduct once every year or less.

4 Miscellaneous Water

Miscellaneous water refers to water used for watering, aquascapes, cleaning, and flush toilets (except when tap water is used).

Hygiene measures related to water supply
Measurement of free residual chlorine 1/7 days (0.1ppm or more)
pH value 1/7 days (5.8 or more and 8.6 or less)
Odor 1/7 days (not abnormal)
Appearance 1/7 days (mostly colorless and transparent)

※In the case of combined residual chlorine, retain at least 0.4 ppm.
※If the supplied water may be significantly contaminated with pathogenic organisms, or if there is a possibility that it may contain a large amount of organisms or substances that may suspect that the pathogenic organisms are contaminated, free residual chlorine contained in the water at the hydrant shall be 0.2 ppm (1.5 ppm for combined residual chlorine).
※Do not use water containing human waste as raw water for watering, aquascapes, or cleaning.

Water quality inspection (conducted once every two months, regularly)
Escherichia coli Not detected
Turbidity 2 times or less

※For turbidity, implement water used for watering, aquascape, and cleaning.

Cleaning of miscellaneous water tanks
Inspection and cleaning of miscellaneous water tanks Periodic cleaning is carried out according to the status of regular inspections.

5. About drainage facilities

Drainage facilities
Cleaning of sewage tanks 1/6 months or less (regular)

※Sewage tanks, etc. refer to sewage tanks, miscellaneous drainage tanks, interceptors, etc.

6 About cleaning

About cleaning
General cleaning of facilities 1/6 months or less (regular)

※In addition to daily cleaning, facility cleaning refers to the removal of lighting fixtures, ventilation openings, walls, and high altitudes, and inspection and cleaning of waste treatment systems as unified cleaning.

7 About control of rats

About control of rats
Inhabitation survey, prevention measures, effect judgment of rats, etc. 1/6 months or less (regular)

※Conduct a unified survey once every six months on the location, habitat, intrusion route, and the status of damage caused by rats, etc., and based on the results of the survey, take necessary measures to prevent the occurrence.
In addition, in areas where food is handled and areas where rats are likely to occur, such as around drainage tanks, interceptors, and waste storage facilities, once every two months, investigate their habitat, etc. Take measures to prevent outbreaks.

8. Provision of books and documents

About books and documents that building owners must prepare
Type of books and documents Storage period

Book documents describing the status of air environment adjustment, water supply and drainage management, cleaning and rat control (including the results of measurement or inspection of these measures and the status of inspection and maintenance of equipment)

5 years
Floor plan and cross-sectional view, and drawings that clarify the layout and system of equipment related to maintenance Years
When the building environmental hygiene management engineer concurrently serves as two or more specific buildings, the result of confirming that the specific building owners, etc. did not hinder the execution of the duties of the building environmental hygiene management engineer (specified building If an opinion is heard from the owner of the maintenance right, the content of the opinion is included.) While the building environmental hygiene management engineer concurrently serves as a building environmental hygiene management engineer for two or more specific buildings at the same time
Other books and documents describing matters necessary for environmental hygiene related to maintenance 5 years

Inquiries to this page

Health Sanitation Division, Medical Care Bureau Health and Safety Department

Telephone: 045-671-2456

Telephone: 045-671-2456

Fax: 045-641-6074

Email address: ir-seikatsueisei@city.yokohama.lg.jp

Return to the previous page

Page ID: 967-713-467

Menu

  • LINE
  • Twitter
  • Facebook
  • Instagram
  • YouTube
  • SmartNews